ID50 Series Panel - Installation, Commissioning & Configuration Manual
Configuration Mode
55
997-263-000-11, Issue 11
January 2010
To change the RS485 Protocol:
1 From the Setup menu screen, press the ‘
4
’ button
on the numeric keypad to enter the Peripheral Options
screen. The RS485 Protocol screen is displayed:
2 Press the ‘
6
’ button repeatedly to step through the
alternative protocol settings.
3 Press ‘
4
’ to return to the Peripherals menu screen.
5.5.4.4 Third Party Datalink Monitoring
This function is only selectable if Third Party was selected
at the RS485 Protocol screen. Monitoring of the third party
datalink can be enabled or disabled as follows:
1 From the Peripheral Options screen, press the ‘
1
button on the numeric keypad to select the RS485
Communications port option. The RS485 Protocol
setup screen is displayed:
2 Press the ‘
2
/
8
’ buttons to scroll through the
Peripheral Options until the Data Link Monitoring
screen is displayed.
3 If required, press the ‘
6
’ button to select DISABLED.
4 Press ‘
4
’ to return to the Peripheral Options menu
screen.
[Setup] RS485 Protocol = NOTIFIER
> : Change ¦ : More < : Exit
[Setup] RS485 Protocol = BFT/LLT
> : Change ¦ : More < : Exit
[Setup] RS485 Protocol = THIRD PARTY
> : Change ¦ : More < : Exit
4
6
[Setup] Data Link Monitoring = DISABLED
> : Change ¦ : More < : Exit
[Setup] Data Link Monitoring = ENABLED
> : Change ¦ : More < : Exit
[Setup] RS485 Protocol = THIRD PARTY
> : Change ¦ : More < : Exit
or
82
6
1