4.12.3 Faults - User Option
This menu option allows the user to view active faults
while the normal active fault display has been overridden
by a higher priority display (alarms). To view Faults, from
the View Mode menu:
1 On the numeric keypad, press the ‘
3
button to select
the Faults display.
2 The LCD automatically displays the last recorded
event first. Viewing commences from this point. Press
the ‘
2
/
8
buttons to scroll through the faults.
Note: Press the ‘
6
’ button to view additional zone text
information. To return to the fault message press
any numeric/cursor key. Alternatively, if no key is
pressed within ten (10) seconds the display reverts
to the fault message. Example fault displays are
given below:
a. Fault condition
b. Fault currently displayed.
c. Total number of faults
logged.
d. Text description of fault.
e. Zone Number.
f. Device Address.
g. Device Type.
h. Time fault was logged.
Note: If no faults are recorded on the system, the
following message is displayed:
3 Press the ‘
4
button to return to the View Mode
menu.
[U0 View] 1:Log 2:Devices 3:Faults
4:Input Events 5:Disabled ¦ : More
FAULT 01 / 03 Z01 M12 MCP 14:55
< - - - Zone Text - - - > < - - - Device Text - - - >
FAULT 01 / 03 Z01 S23 TMP 14:55
NO REPLY FROM DEVICE >
The system has NO faults present
<:Exit
FAULT 01 / 03 Z01 M12 MCP 14:55
NO REPLY FROM DEVICE >
ABC DE F G H
2
8
6
3
AWACS
TM
Devices (ID60 only)
The ID60 panel allows the configuration of all sensor
types, except HEAT sensors, to use the AWACS
TM
multi-
sensing algorithm. For these devices an additional screen
is available which displays the current percentage values
for alarm and pre-alarm.
[U0 Sensor nn - AVS] >: Next ¦ : More
AWACS - Alarm: 000%, Prealarm: 000%