EasyManua.ls Logo

Honeywell NOTIFIER LDM Series - Lamp;LED Wiring

Honeywell NOTIFIER LDM Series
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LDM Series Instruction Manual — P/N 15885:H3 8/12/2019 19
Lamp/LED Wiring Wiring Considerations
below. If this module is used to drive both power-limited and nonpower-limited circuits, connect relays 1 to 16 to power-limited circuits
and connect relays 17 to 32 to nonpower-limited circuits or vice versa. Use an appropriate power-limited power supply which is UL
listed for fire alarm systems to provide power for the power-limited circuits.
4.9 Lamp/LED Wiring
Figure 4.8 illustrates LEDs being powered by the 5V output from LDM-32, J11 pin 1.
Figure 4.9 illustrates LEDs being powered by the 24V output from LDM-32, J9 pin 3.
Power-
Limited
Circuits
Nonpower-
Limited
Circuits
LDM-R32
Figure 4.7 Wiring Requirements
NOTE: All LEDs/lamps being driven by the LDM series must be located in the same room as the modules. Use cable kits for wiring from
connectors on LDM.
J11
+5
Common
J6
J5
J4
SWITCH
MATRI X
LAMP
POWER
OUTPUTS
J7
J8
J10
J9
Point Status LEDs:
Use red for alarm points,
yellow for trouble points, and
green for output points
Use 680 W, 1/4 watt resistors for
each point if using 2 mA LEDs.
Custom
Graphic
Display
Wiring is
not
supervised
System
Trouble LED
(Yellow)
Note: All LEDs must be in the same room as the LDM modules.
Figure 4.8 Typical LDM-to-Graphics Display Connection @ 5VDC

Table of Contents

Related product manuals