5. Cables
5.3. Transmitter connection status
Revision 3 OneWireless XYR 6000 Transmitter Professional Installation Guide 15
September 2012
5.3 Transmitter connection status
Table 5-3 Lightning Arrestor to Antenna Cable Specifications
Honeywell
Part Number
Cable Type Connector
Type
Frequency
(GHz)
Length
(m)
Loss
(dB)
50018278-001 400 Series N male to N male 2.4 1 1
50018278-003 400 Series N male to N male 2.4 3 2
50018278-010 400 Series N male to N male 2.4 10 3
5.4 Antenna Lightning Arrestors
Table 5-4 Lightning Arrestor Specifications for Remote Antenna(s)
Honeywell
Part
Number
Manufacturer
Manufacturer
Part Number
Specification
Connector
Type
Frequency
(GHz)
Attenuation
(dB)
50018279-
090
ALTELECON AL-NFNFB-9 50 ohm
N Female
to N
Female
0 – 3 0.4 (max)
The lightning surge arrestor must be properly grounded in order to perform per specification. Connecting
to local ground using a No. 12 (4 mm2) copper conductor is recommended. See the installation manual for
other details.
Figure 5-1 Lightening Surge Arrestor (Altelecon AL-NFNFB-9) 50018279-090