Revision 2 RMA803 Remote Indicator User's Guide 20
Input Calibration
Low Point
[CAL Lo ]
Input Calibration Low Point
This selection allows the user to
perfom calibration for 4 mA.
Note: You must connect a current
meter to the transmitter to monitor
the loop output. And the
device/loop current need to set to
exact 4mA.
Press to
enter menu
selection
Menu to
select
number.
to enter
and shift to
the next digit
to the right
Input Calibration
High Point
[CAL Hi]
Input Calibration High Point
This selection allows the user to
perform calibration for 20mA.
Note: You must connect a current
meter to the transmitter to monitor
the loop output. And the
device/loop current need to set to
exact 20mA.
Pressure/
Temperature
Base Units
[B UNIT]
Pressure Units:
inH2O@39°F
mH2O@4°C
cmH2O@4°C
torr
mmH2O@68°F
ftH2O@68°F
inH2O@68°F
inH2O@60°F
torr, atm
Pa, kPa, MPa
gf/cm2, kgf/cm2
psi
mbar, bar
inHg@0°C
mmHg@0°C
mmH2O@4°C
Temperature Units:
°C
°F
°R
K
mV
Ohm
Choose appropriate engineering
Base Unit of transmitter units from
list as per Pressure or Temperature
PV selection.
Press to
enter Menu
selection
Menu to
select level.
to Enter
NOTE:
BUNIT should not be changed for STT700 DE device & STT250 DE device in both digital and
analog mode