SEC-H-600 SECURITY CONTROLLER
95-7759—07 22
Digital Input
The SEC-H-600 controller has three (3) digital inputs, located on a 4-position connector next to supervised input connector (see
Fig. 4 on page 12). Under the connector, terminals are labeled GND, DI1, DI2, DI3. This means when wiring, as many as three
conductors can be landed to the common GND terminal.
Each digital input can monitor dry contacts, either normally-open (N.O.) or normally-closed (N.C.). All three inputs are
unsupervised—no end-of-line resistors are required. Figure 12 below shows example wiring to all three digital inputs of the SEC-
H-600 controller.
Fig. 12. Digital input wiring example to Security Controller.
NOTE: The WEBs-AX Security Application is pre-configured to support the following connections:
DI1 — Tamper switch (typically for enclosure door)
DI2 — Battery status bad (if contacts available)
DI3 — AC power fail (if contacts available)
Depending on the installation, not all DIs may require connection. In almost all cases, input DI1 is wired to the tamper
switch of the WEBs-AX Security Enclosure housing the Security Controller.
DI1
DI2
DI3
PS+
PS–
BT+
BT–
GND
GND
SI6
SI1
SI2
SI3
SI5
SI4
GND
GND
AC Power Fail
Shields
Security
Controller
SEC-ENC-H-2
Enclosure for
Security
Controller
NC
or
NO
Tamper
Switch
NC or NO
4-position connector for
Digital Inputs
Tape back shield at
device contact end (typ).
NC
or
NO
Battery Status Bad