SEC-H-600 SECURITY CONTROLLER
15 95-7759—07
SECURITY I/O WIRING
Security I/O wiring is covered in the following subsections:
“Door Terminal Associations,” page 15
“Reader Input,” page 17
“Supervised Input,” page 18
Relay Output,” page 20
“Digital Input,” page 22
Door Terminal Associations
The SEC-H-600 controller provides access control for two doors. For each door, the controller allocates:
One Reader Input (for a Wiegand-type, 12V reader)
Two Supervised Inputs: one for door switch monitor, one for REX (request-to-exit)
One Relay Output: for door strike control.
A default convention is used for the logical association between reader inputs, supervised inputs, and relay outputs for each door,
as shown in Table 4 below.
NOTE: Terminal associations shown in Table 4 also apply if wiring a SEC-H-R2R (2 reader) expansion module.
See the following sections below for more details:
Example Door 1 Wiring
Other Terminal Associations
Table 4. Door mapping to security I/O terminal points.
Door Reader Input
Supervised Input Terminals (with GND)
Relay Output Terminals
Door Lock
Door Switch
Monitor
Request to Exit
(REX)
Door 1 Card Reader 1 SI1 SI2 1 (C1 and NO1, or NC1)
Door 2 Card Reader 2 SI3 SI4 2 (C2 and NO2, or NC2)