EasyManua.ls Logo

Honeywell SEC-H-600 - Reader Input

Honeywell SEC-H-600
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SEC-H-600 SECURITY CONTROLLER
17 95-7759—07
Reader Input
The SEC-H-600 controller has two door reader inputs, each supporting a Wiegand-type 12Vdc reader. Each reader input has a 7-
position connector, on the circuit board labeled as Card Reader 2 and 1 (see Fig. 4 on page 12). Typical wiring is shown below in
Fig. 8. Pinouts for each card reader connector are shown in Table 5.
NOTE: A door wired to a reader input has other I/O points, see “Door Terminal Associations,” page 15.
Fig. 8. Reader wiring to Security Controller.
Reader Wiring Notes
Mount the reader, referring to the specific manual for that reader for instructions.
Use shielded, twisted-pair, cabling (Belden #8725 or #8723 or equivalent, as needed) to connect the reader to the Security
Controller. Maximum cable distance is 500 feet (152m).
Run this cabling from the reader to the Security Controller, bringing it through an appropriate knockout in the enclosure used.
Allow sufficient slack cable for servicing.
Tie all shield wires together, and connect to the designated grounding point at the enclosure. SeeFig. 5 on page 13.
Place the appropriate wires in the appropriate screw terminals of the 7-position reader connector. Refer to the pinouts in
Table 5 above for reader input designations. Figure 8 above lists typical wiring colors.
Table 5. Pinouts for Card Reader Inputs
Terminal Terminal Name Terminal Notes Typical cabling colors
DC+ +12Vdc to Reader Always wire these four terminals to the
corresponding reader terminals.
Typically Red wire.
GND Ground Typically Black wire.
D0 Reader Data 0 Typically Green wire.
D1 Reader Data 1 Typically White wire.
AX1 Auxiliary 1 Optional, wire to reader’s Green LED
control
At reader, typically Orange wire.
AX2 Auxiliary 2 Optional, wire to reader’s Red LED control At reader, typically Brown wire.
AX3 Auxiliary 3 Optional, wire to reader’s Beeper control At reader, typically Blue or Yellow
wire.
GND
DC+
AX3
AX1
D1
AX2
D0
CARD
READER
n
Red (+12Vdc)
Black (Ground)
Green (Data 0)
White (Data 1)
optional 1
optional 2
optional 3
Reader
Shields
NOTE: Maximum current rating for
both reader inputs (combined) is:
• Peak current maximum: 0.40A
• Average current maximum:0.30A

Related product manuals