Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08-2016
38
13 Menu’s and Advanced Conguration
13.1 Abort Function
In Review Mode or Configuration Mode the user can escape one step back from the
current position using the Abort Function. To do this the user must activate the Enter
switch for more than 3 seconds with the Magnetic Wand. Switching between each pair of
modes or between menus and sub menus are shown in the following table.
From To Example
Review Mode Monitoring Mode
Activate Enter switch for more than 3
seconds while in Review Mode
Conguration Mode Monitoring Mode
Activate Enter switch for more than 3
seconds while navigating menus in the
Conguration Mode
Conguration Mode
sub menu
Conguration Mode
main menu
Activate Enter switch for more than 3
seconds while in a sub menu
Table 10: Transmitter menu switching
13.2 Conguration Mode
The table below shows the functions available via the configuration menu that can be
displayed on the transmitter and accessed using the Magnetic Wand.
The instrument will show the main Menu when the “Enter” switch is activated with the
Magnetic Wand and held for at least 3 seconds.
The Menu is password protected to prevent any unauthorized changes. The password is
initially disabled and the default password is ‘0000’. If the default password is changed
to other than ‘0000’, then the password is enabled automatically and requested when
entering Conguration Mode.
With the Menu showing, the following functions can be performed: calibration, bump test,
sensor selection and configuration of parameters such as measuring range, calibration
gas level, calibration interval, inhibit current, inhibit timeout, alarm setting, relay setting,
password change, location setting, temperature unit reading, force analogue output and
alarm function checks.
While in Conguration mode, the output current of the transmitter is inhibited to prevent
false alarms.
Names, displays and descriptions for each menu item in Conguration Mode are shown in
the following table.