Sensepoint XCD RFD Technical Manual SPXCDHMRFEN Issue 4_08-2016
39
Menu Display Description
Set Calibration
Execute zero/span calibration
Set calibration gas level
After zero, the option exists to proceed with
span calibration, or return to the Menu.
Select Sensor
Select the type of sensor from the sensor
list. This menu is only available for
ammable / IR sensor.
Select Gas
Select the type of gas from the list. This
menu is only available for ammable / IR
sensor.
Set Range
Set measuring range
Congure Inhibit
Select inhibit current
Set timeout option (5 minute increments)
Set Password
Enable/disable password
Set password
Default – no password (Select ‘0000’)
Set Calibration Interval
Set calibration interval, 30 to 365 days
User congurable option to display warning
Bump Test
Execute a ‘bump’ test to check gas
response of the sensor.
Force Current
Force analogue output to test functionality
of GD control system during system
commissioning.
Set Alarms
Set alarm 1, alarm 2 levels, functionality
and operation (none/falling/rising)
Set Relays
Set relay 1,2,3 type (alarm 1, alarm 2,
fault and inhibit) and action (energized/
de-energized)