Sensepoint XCD RFD Technical Manual   SPXCDHMRFEN Issue 4_08-2016
42
13.2.1 Conguration mode operation table
Configuration mode allows the user to perform calibration and configure parameters 
such as full scale range, calibration gas level, calibration interval, inhibit current & 
timeout, alarm settings, relay settings, set a password, etc. To activate Configuration 
mode hold the magnet over the ENTER switch for at least 3 seconds and then remove. 
Conguration mode can be password protected to prevent unauthorized personnel from 
changing parameters. Initially the password is set to ‘0000’ meaning it is disabled. While in 
Conguration mode, the output current of the detector is inhibited to prevent false alarms.
Use the table below to help navigate the  menus and make configuration changes. The 
menus are shown in the left hand column. Use 
 to select the required menu and ‘
’ 
to enter. Follow the information and instructions in the table from left to right from the 
required menu.
OK
OK
OK
OK
SEt 
CAL
1
GAS NAME, ZERO 
CONCENTRATION AND 
FLASHING ‘ 
 ’ ICON 
DISPLAYED. APPLY ZERO 
GAS AND USE ‘
’ WHEN 
READING IS STABLE. ‘ZEro 
PASS’ DISPLAYED IF OK, 
‘ZEro FAIL’ IF NOT.
‘SPAN’ DISPLAYED AND 
‘YES’ FLASHING TO 
ASK IF YOU NOW WANT 
TO PERFORM SPAN 
CALIBRATION. USE ‘
’ 
TO PROCEED OR USE 
 TO SELECT ‘No’ 
AND RETURN TO MENU 
MODE.
‘GAS’ TARGET 
CONCENTRATION 
FLASHING AND ‘ 
 ’ 
ICON DISPLAYED. 
USE 
 TO 
CHANGE GAS 
CONCENTRATION 
AND ‘
’ TO START 
SPAN CALIBRATION.
GAS NAME, CURRENT 
CONCENTRATION AND 
FLASHING ‘ ’ ICON 
DISPLAYED. APPLY 
SPAN GAS AND USE ‘
’ 
WHEN READING STABLE. 
IF OK ‘PASS’ & ‘PurG’ 
DISPLAYED (IF FAIL 
‘SPAN FAIL’ DISPLAYED 
AND RETURNS TO 
MENU). REMOVE SPAN 
GAS. WHEN READING 
<50% OF SPAN POINT, 
COUNTDOWN BEGINS & 
UNIT RETURNS TO MENU 
MODE.
SEt 
rAn9
BAR GRAPH INDICATING 
CURRENT RANGE, ‘rAn9’ 
DISPLAYED & CURRENT 
RANGE FLASHES. USE 
 
TO SELECT DIFFERENT 
RANGE
IF RANGE IS CHANGED, 
‘CAL’ DISPLAYED AND 
‘YES’ FLASHING TO 
ASK IF YOU NOW 
WANT TO PERFORM 
CALIBRATION. USE ‘
’ 
TO PROCEED OR USE 
 TO SELECT ‘No’.
IF RANGE IS 
CHANGED, ‘ALrm’ 
DISPLAYED AND 
‘YES’ FLASHING TO 
ASK IF YOU NOW 
WANT TO MODIFY 
ALARM SETTINGS. 
USE ‘
’ TO PROCEED 
OR USE 
 TO 
SELECT ‘No’ AND 
RETURN TO MENU 
MODE.
UNIT RETURNS TO MENU 
MODE
ConF 
Inhb
‘Inhb’ DISPLAYED WITH 
‘     ’ ICON FLASHING. 
CURRENT INHIBIT mA  
VALUE FLASHES. USE 
 
TO SELECT NEW VALUE 
‘tImE’ DISPLAYED WITH 
‘     ’ ICON. FLASHING 
CURRENT INHIBIT 
TIMEOUT PERIOD 
(MINUTES) FLASHES. 
USE 
 TO SET 
NEW TIMEOUT. (IF 
SET TO 0 OUTPUT 
IS PERMANENTLY 
INHIBITED)
UNIT RETURNS TO 
MENU MODE
SEt 
PASS
‘PASS’ DISPLAYED WITH 
FIRST DIGIT PLACE ICON 
OF THE PASSCODE 
FLASHING. USE 
 TO 
SELECT 1
ST
 DIGIT OF 
CURRENT PASSWORD. 
USE 
 TO MOVE TO NEXT 
DIGIT AND SET REST OF 
PASSCODE.
UNIT RETURNS TO 
MENU MODE
CAL 
Int3
2
‘Int’ DISPLAYED WITH 
CURRENT CALIBRATION 
INTERVAL FLASHING. 
USE 
 TO CHANGE 
INTERVAL.
‘duE’ DISPLAYED AND  
‘No’, ‘LCd’ OR ‘ALL’ 
FLASHING. USE 
 
TO SELECT REQUIRED 
CAL DUE WARNING 
OUTPUT.
UNIT RETURNS TO 
MENU MODE