SPYDER MODEL 7 VAV CONTROLLER  INSTALLATION INSTRUCTIONS
25 31-00475-01
NOTE:
The 120 Ω termination resistor must be inserted 
directly into the terminals of both end devices.
NOTE:
The controller is insensitive to bias voltages due to 
the failsafe chipset inside, and it can share the 
BACnet bus with other devices with or without 
bias voltages.
BACNET MSTP CONTROLLER
Automatic MAC Addressing
In contrast to other controllers, the Spyder Model 7 
MSTP controllers feature automatic MAC addressing. 
NOTE:
When the dip switches are set to all-ON or all-OFF, 
the controller will run in Auto MAC mode. Do not 
attempt to program a MAC address outside of Min 
MAC and Max MAC (0 to 127).
The MAC addresses are not assigned in sequential 
order. Controllers are assigned MAC addresses that are 
not already in use by another BACnet MSTP device in 
the range of Min MAC to Max MAC.
In the scenario depicted in Fig. 29, some of the 
controllers in the BACnet MSTP network do not feature 
automatic MAC addressing; therefore, their MAC 
addresses are assigned manually. Thus, when a new 
Spyder Model 7 BACnet MSTP VAV is added to the 
network and its automatic MAC addressing function is 
triggered, it will assign itself an available (unused) MAC 
address within the range of Min MAC and Max MAC 
values.
Fig. 29  Automatic MAC Addressing
All Spyder Model 7 BACnet MSTP VAV controllers are 
BACnet MSTP clients. Every client performs periodic 
polling for the possible appearance of new clients. Each 
client knows the identity of the next client on the 
BACnet MSTP bus and to which it must pass the token. 
The polling process includes searching for new clients 
with MAC addresses lying between their own MAC 
address and that of the next client.
The property Max Master specifies the highest-
allowable address for client nodes. Max Master is set to 
126 by default, which means that it can support up to 
124 BACnet MSTP VAV controllers, one supervisor, and 
one BACnet client (tool) per BACnet MSTP network.
The following properties are writable and can be 
changed:
• Max Master
• Min MAC
• Max MAC
• MAC address. 
Manual configuration of the MAC 
Address
The MSTP MAC address for each device must be set to a 
unique value in the range of 1-126 on an MSTP network 
segment. Seven DIP switches on the Spyder Model 7 
MSTP BACnet controller are used to set the controller's 
MAC address.
Fig. 30  MSTP MAC Address Details
To set the MAC address of a Spyder Model 7 BACnet 
MSTP VAV controller:
1. Find an unused MAC address on the BACnet MSTP 
network to which the Spyder Model 7 BACnet 
MSTP VAV controller connects.
2. Locate the DIP switch bank on the Spyder Model 7 
BACnet MSTP VAV for addressing.
3. Power off the Spyder Model 7 BACnet MSTP and 
set the DIP switches for the MAC address you want.
4. Add the value of DIP switches set to ON to deter-
mine the MAC address. See Table 20.
CONTROLLER WITH MANUAL MAC ADDRESSING
CONTROLLER WITH AUTOMATIC MAC ADDRESSING
#maxMaste
BACnet MSTP
Max Master
WEB-8000
Table 19  Default Values
Default
Max Master
Default 
MinMAC
Default 
MaxMAC
Default 
Baud 
Rate
126 1 126 76800
Table 20  DIP Switch values for MSTP MAC Address
DIP 1 2 3 4 5 6 7
VALUE 1 2 4 8 16 32 64