EasyManuals Logo

Honeywell STT25D User Manual

Honeywell STT25D
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
Smart Temperature Transmitter STT250 – Operator Manual 7
4. BENCH CHECK INSTALLATION/COMMISSIONING
4.1 Unpacking
Unpack the unit and verify the contents are as ordered.
4.2 Equipment
If a bench check is intended, the equipment needed is:
ü an input sensor suitable for the required application or an equivalent calibrator
which can simulate milli-volts, resistance temperature detector, thermocouple or
resistance (ohms) inputs,
ü a nominal 24 Vdc power supply with less than 100 mV peak ripple and able to
supply at least 40 mA,
ü a Smart Field Communicator (SFC) with STT25M or STT25D or HART
Communicator (model 275) with STT25H,
ü connection wiring and 250 ohms resistor,
ü a Digital Voltmeter (DVM) with range covering 0-5 Vdc. If a high speed sampling
DVM is used, a 1 Hz (160 msec.) averaging filter is recommended.
NOTE: If you are going to check calibration using a thermocouple input, ensure
that the cold junction temperature is stabilized. After connecting and powering
up all equipment, including the transmitter, protect the transmitter from air
drafts and allow at least 1 hour before taking readings.
4.3 Installation
Connect the equipment as in Figures 2 and 3. For more detailed wiring drawings, refer
to drawings listed in Section 5.4.
ATTENTION: Do not connect power supply to sensor wiring terminals.
24 Vdc
Power supply
SFC
or
HART
communicator
4-20 mA
DVM
250 ohms
+
-
+
-
Figure 2: Bench Check Wiring Connections

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell STT25D and is the answer not in the manual?

Honeywell STT25D Specifications

General IconGeneral
BrandHoneywell
ModelSTT25D
CategoryTransmitter
LanguageEnglish

Related product manuals