VISIONPRO
®
8000 WITH WI-FI
®
23 33-00096—01
402 Type of Override
Standard
Initiate Occupancy
Standard Commercial Standard:
The system maintains temperatures
programmed for the occupied and unoccupied
time periods. Pressing OVERRIDE will allow the
user to make a temporary schedule change.
Initiate Occupancy:
The system maintains temperature at an energy
saving level until the user touches the message
center area on the thermostat. Note: The
message center displays Press HERE to Start
Occupancy. The system will then maintain a
comfortable temperature until the occupied
period ends. This option is recommended for
cost savings when the workplace is used
infrequently or arrival times change from day to
day (example - schools). After the user touches
Press HERE to Start Occupancy, the user will
still be able to perform a standard OVERRIDE of
the schedule.
403 Override Duration
No Limit
1 to 12 Hours
3 hours Commercial When the user presses the OVERRIDE button,
the thermostat will maintain the new
temperature for at least 1 hour. The user can
adjust the Hold Until time from 1 hour to the
amount set for the Override Duration (1-12
hours). Default setting is 3 hours. If set to No
Limit, the user can adjust the Hold Until time up
to 24 hours.
405 Min. Heat
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
5° F/hr Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a cold day in your region. Default setting is
5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day
in your region to be associated with the
Minimum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save energy
during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes