VISIONPRO
®
8000 WITH WI-FI
®
39 33-00096—01
INSTALLER TESTS
Use the installer tests to check out the system:
• Equipment Test: Tests the heating, cooling, fan, and IAQ
equipment. The test allows you to manually call for each
system to ensure the equipment and thermostat operate
properly. Any minimum off timers are ignored during the
system test. You can test the following equipment:
—Heat
—Em Heat
—Cool
—Fan
— Humidification
— Dehumidification
— Ventilation
— Economizer
— Time of Day
Accessing Installer Test
1. Press MENU on the home screen, then scroll down to
Installer Options and press SELECT.
2. Enter the password (date code) when prompted. See
“Finding Your Password (Date Code) to Access Installer
Options” beginning on page 9 for more information.
3. Scroll down to Installer Test and press SELECT.
Fig. 23.
Equipment Damage Hazard.
Minimum compressor off time is bypassed during
the Equipment Test
Avoid cycling compressor quickly.
Using the Installer Test
1. Select the equipment you want to test and press the
arrow buttons to turn the equipment on/off. Press Back to
test the remaining equipment.
NOTE: The time out for the Equipment Test mode is 30
minutes (if there is no keypress for 30 minutes,
the thermostat will automatically exit the Equip-
ment Test).
Fig. 24.
Fig. 25.
2. Run Time and Discharge temperature are displayed for
heating and cooling tests (requires Discharge Air Sen-
sor). See Fig. 26.
The Discharge temperature updates every 30 seconds
during the test. The Run Time counter starts over when
the next stage is turned on.
Fig. 26.