VISIONPRO
®
8000 WITH WI-FI
®
33-00096—01 24
405 Min. Heat
Recovery Outdoor
Temp
Off
-20° F to 100°F
0° F Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Minimum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Minimum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a cold day in your region. Default setting is
5° F / hour.
If an outdoor sensor is installed, set an Outdoor
Temperature that is representative of a cold day
in your region to be associated with the
Minimum Recovery Ramp Rate. The
thermostat will begin recovery at the optimal
time based on a calculated ramp rate, allowing
the system to recover on time and save energy
during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature. If there is no outdoor sensor, the
Minimum Recovery Ramp Rate is used.
406 Max. Heat
Recovery Ramp
Rate
Off
1° F/hr to 20° F/hr
8° F/hr Commercial Off: The heating system will begin recovery at
the time that is scheduled.
When a Maximum Recovery Ramp Rate is set,
the thermostat will begin recovery early to
ensure the temperature is reached at the
scheduled time.
Set a Maximum Recovery Ramp Rate based on
the rate that the heating system can recover at
for a mild day in your region. Default setting is
8° F / hour.
Set an Outdoor Temperature that is
representative of a mild day in your region to be
associated with the Maximum Recovery Ramp
Rate. The thermostat will begin recovery at the
optimal time based on a calculated ramp rate,
allowing the system to recover on time and save
energy during changing outdoor conditions.
During recovery, the setpoint changes at a rate
in degrees per hour depending on the outdoor
temperature.
Table 2. Installer Setup (ISU) Table. (Continued)
ISU
Number
Installer Setup
Name Settings Default
Residential,
Commercial
or Both Notes