Page 19
792518-001 Edition 2
ENGLISH
ENGLISH
6. Technical Specifications
6.1 HPE R1500 G4 NA UPS and HPE R1500 G4 JP/TWN UPS
Rack HPE R1500 G4 NA UPS HPE R1500 G4 JP/TWN UPS
Output Power @ 120V
1440 VA
1100W
—
Output Power @ 100V
—
1200 VA
900W
AC Input power
• Rated input voltage Single phase 100-125V
• Input voltage range
80 to 162V (-10% to +5%)
(1)
• Input frequency range
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
•Voltage
100/120V (-10% to +5%)
(3)
•Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•Standard 6 x 6V
9 Ah
Environment
• Operating
temperature range
32 to 104°F/0 to 40°C
• Storage
temperature range
5 to 122°F/-15 to +50°C
• Relative humidity 0 to 90% (without condensation)
•Noise level < 40 dBA
(1) The high and low thresholds can be adjusted using UPS settings.
(2) Up to 40 Hz in low-sensitivity mode (programmable using UPS settings).
(3) Adjustable to 100/120/125V, but must be set to the identical AC power source value.
Caution: Toreducetheriskofre,connectonlytoacircuitprovidedwith20Amaximumbranchcircuit
overcurrent protection in accordance with the National Electric Code, ANSI/NFPA 70.
Filter
Transformer
AVR Charger Inverter
Battery