Page 9
792518-001 Edition 2
ENGLISH
ENGLISH
2.3 Display functions
Press the button to activate the menu options. Use the and buttons to scroll through the menu
structure. Press the button to select an option. Press the button to cancel or return to the previous
menu.
Display Function Menu
Main menu Submenu Display information or Menu function
Measurements
—
Load W VA/Load A pf/Output V Hz/Input V Hz/
Battery V min/Efficiency/Power usage
Control Load Segments Group 1: ON/OFF
Group 2: ON/OFF
These commands overrule user settings for load segments.
Start battery test Starts a manual battery test
Reset fault state Clears active faults (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage Clears power usage measurements
Settings Local settings Sets general parameters
Input/output settings Sets Input and output parameters
ON/OFF settings Sets on and off conditions
Battery settings Sets battery configuration
Fault log
—
Displays event log or alarms
Identification
—
UPS Type/Part Number/Serial Number/Firmware release/Com
card address
2.4 User settings
The following table displays the options that can be changed by the user.
Description Available settings Default settings
Local settings
Language
[English] [French] [German]
[Spanish] [Italian] [Portuguese]
[Russian]
Menus, status, notices and alarms,
UPS fault, event log data and settings
are in all supported languages.
English
User selectable when UPS is
powered the first time.
LCD settings Allows LCD screen brightness and
contrast to be adapted to room light
conditions.
—
Audible alarm [Enabled] [Disabled on battery]
[Always disabled]
Allows you to enable or disable the
audio alarm if an alarm occurs.
Enabled
In/Out settings
Output voltage* [100V] [120V] [125V]
On INTL models: [200V] [208V] [220V] [230V]
[240V]
User selectable when UPS is
powered the first time.
*Important: TheoutputvoltageoftheUPSmustbesettothesamenominalvoltageasthefacility
inputvoltageforoptimumUPSperformance.
Input thresholds [Normal mode] [Extended mode]
Extended mode reduces lower input
voltage to 70V before UPS transfers
to battery.
This can be used if the load can
withstand low voltage supply.
Normal mode
Sensitivity [High] [Low]
High: For sensitive equipment, the
UPS will easily transfer to battery
when utility conditions deteriorate.
Low: For less sensitive equipment,
the UPS will not transfer to battery
when utility conditions deteriorate.
High
Load segments -
Auto start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected equipment is powered
after the specified delay.
Group 1: 3 s
Group 2: 6 s
Continued
2. User Interface