Page 20
792518-001 Edition 2
ENGLISH
6. Technical Specifications
6.2 HPE R1500 G4 INTL UPS
Rack HPE R1500 G4 INTL UPS
Output Power @ 230V
1550 VA
1100W
Output Power @ 200V/208V
1395 VA
990W
AC Input power
• Rated input voltage Single phase 200-240V
• Input voltage range
160 to 294V
(1)
• Input frequency range
47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)
(2)
Output on battery power
•Voltage
200/208/220/230/240V (-10% to +5%)
(3)
•Frequency 50/60 Hz ±0.1 Hz
Battery (sealed lead acid, maintenance free)
•Standard 6 x 6V
9 Ah
Environment
• Operating
temperature range
32 to 104°F/0 to 40°C
• Storage
temperature range
5 to 122°F/-15 to +50°C
• Relative humidity 20 to 90% (without condensation)
•Noise level < 40 dBA
(1) The high and low thresholds can be adjusted using UPS settings.
(2) Up to 40 Hz in low-sensitivity mode (programmable using UPS settings).
(3) Adjustable to 200/208/220/230/240V, but must be set to the identical AC power source value.
When the UPS is used in the EU area, use an external circuit breaker in front of the line with rating 16A,
250V which is IEC/EN 60898-1 standard compliant.
When the UPS is used in th NA area, use an external circuit breaker in front of the line with rating 20A,
250V.
Filter
Transformer
AVR
Charger Inverter
Battery