Figure 2-15 Securing Each Caster Cover to the Server
17. Wheel kit installation is complete when both caster covers are attached to the server, and
the front bezel and all covers are installed.
Figure 2-16 Completed Server
Installing the Power Distribution Unit
The server may ship with a power distribution unit (PDU). Two 60 A PDUs available for the
server. Each PDU 3 U high and is mounted horizontally between the rear columns of the server
cabinet. The 60 A PDUs are delivered with an IEC-309 60 A plug.
The 60 A NEMA
2
PDU has four 20 A circuit breakers and is constructed for North American
use. Each of the four circuit breakers has two IEC
3
-320 C19 outlets providing a total of eight
IEC-320 C19 outlets.
2. The acronym NEMA stands for National Electrical Manufacturers Association.
3. The acronym IEC stands for International Electrotechnical Commission.
Installing the Power Distribution Unit 43