38 HP StorageWorks XP10000 Disk Array Site Preparation Guide
Primary and second rack figure notes and floor loading
The following explanatory notes apply to Figure 4 (page 36) and Figure 5
(page 37).
*1: Clearance (a+b) depends on the floor load rating and clearance “c”.
Required clearances for various floor load ratings are shown below.
*2: Clearance between racks must be at least 10 mm. If the kickplate
is installed after rack placement, allow 100 mm.
Additional notes:
Decide actual clearances in consultation with the construction
specialist responsible for installation. They may vary depending on the
size and layout of the system and building conditions.
When multiple disk arrays are arranged in a row, base your clearance
values on the requirements of the largest disk array.
Generally, clearances (“c”) should be as large as allowable.
Table 8. Floor load rating for service clearances (twin rack)
Floor
load rating
(kg/m
2
)
Required clearance (a + b) mm
Clearance (c) mm
c = 0 c = 200 c = 400 c = 600 c = 1000
500 100 0.00 0.00 0.00 0.00
450 300 200 0.00 0.00 0.00
400 600 400 300 200 0.00
350 1000 800 600 500 200
300 1600 1300 1100 900 600