62 HP StorageWorks XP10000 Disk Array Site Preparation Guide
AC line voltage requirements
The AC power requirements are essentially the same for both the primary
and the second racks except as indicated in Table 16 note 2. Each rack
operates on 200 VAC nominal, 20-amps, 50 or 60 Hz, single-phase power.
An independent branch circuit and circuit breaker is required for each AC
input power cord.
The following table lists specific power requirements.
Table 16. Primary and secondary rack power requirements
Nominal rated voltage (VAC)
Parameter 200 208
1
220 230 240
Minimum operating voltage (VAC) 184 191 202 212 221
Maximum operating voltage (VAC) 212 220 233 244 254
Rated line current per power cord
2
16A 16A 16A 16A 16A
Number of power cords
3
44444
Recommended circuit breakers 20A 20A 20A 20A 20A
Number of circuit breakers 44444
1 60 Hz only.
2 Rated line current is the maximum allowable current under worst case conditions. This value applies to each individual
power cord and is specified in RMS amperes.
3 For the second rack, four power cords and circuit breakers are strongly recommended even though a minimum
configuration containing only one expansion disk chassis requires only 2 power cords and 2 circuit breakers. If a second
expansion disk chassis is added to the second rack, four power cords and four circuit breakers are required.