42 HP StorageWorks XP10000 Disk Array Site Preparation Guide
Shock
Heat dissipation and power consumption
Table 13 describes the heat dissipation and power consumption of the
XP10000 when loaded with the maximum number of disk drives.
Table 12. Shock specifications
Condition Specification
Operating None
Nonoperating 8 G, 15 ms
Shipping and storage (product packed in
factory packing)
Horizontal:
1
Incline impact: 1.22 m/s
Vertic al :
2
Rotational edge: 0.1 m
1 See ASTM D5277-92 Standard Test Methods for Performing
Programmed Horizontal Impacts Using an Inclined Impact Tester.
2 See ASTM D6055-96 Standard Test Methods for Mechanical Handling of
Unitized Loads and Large Shipping Cases and Crates.
Table 13. Heat dissipation and power consumption specifications
Parameter
Primary
Rack
Second
Rack
Full array
Power consumption (kVA) 4.8 3.0 7.8
Heat dissipation (kW) 4.6 3.0 7.6
BTUs per hour 15700 10200 25900
Kcal per hour 3960 2600 6560