Table 5 Weight specifications with modular PDUs, Rack 2
40A24A and 32A
lbskgslbskgs
725.71338.92742.03355.24Single couplet
1571.71723.471588.03739.79Single couplet with maximum storage added
1127.70521.641144.02537.96Two couplets
2819.701290.732836.021307.05Two couplets with maximum storage added to couplets
Power/PDU requirements
Two power outlets are required for the each couplet. But it is strongly recommended that each rack
be installed with four outlets to allow for ease of expansion, even if the rack has only one couplet.
Power specification
The power factor is close to unity.
Miniature Circuit Breakers (MCBs), type C, are required to prevent tripping with the initial power
on surge of the racks.
Table 6 Power specification at 220V, single rack installed
BTU/hourAVWASingle rack configuration
9960.762905.762833.689.541 couplet with minimum storage
19692.765563.765425.6819.741 couplet with maximum storage
16563.144801.644682.5217.522 couplets with minimum storage
36027.1410117.649866.5237.922 couplets with maximum storage
Table 7 Power specification at 220V, both racks installed
BTU/hourAVWA2–rack configuration
25929.527407.267223.4228.583 couplets with minimum storage
55125.5215381.2614999.4259.183 couplets with maximum storage
32531.909303.149072.2636.564 couplets with minimum storage
71459.9019935.1419440.2677.364 couplets with maximum storage
Table 8 Power specification at 240V, single rack installed
BTU/hourAVWASingle rack configuration
9946.482953.342846.289.481 couplet with minimum storage
19678.485695.045488.5620.881 couplet with maximum storage
16541.724886.964709.8017.522 couplets with minimum storage
36005.7210370.369994.3640.322 couplets with maximum storage
Table 9 Power specification at 240V, both racks installed
BTU/hourAVWA2–rack configuration
25900.967537.247263.9228.423 couplets with minimum storage
55096.9615762.3415190.7662.623 couplets with maximum storage
Power/PDU requirements 7

Other manuals for HP StoreOnce B6000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP StoreOnce B6000 Series and is the answer not in the manual?

HP StoreOnce B6000 Series Specifications

General IconGeneral
BrandHP
ModelStoreOnce B6000 Series
CategoryStorage
LanguageEnglish

Related product manuals