Specifications 25
Battery runtime
Load, percent Load, watts Estimated battery runtime at 100% battery charge
20 100 45 minutes
50 250 15 minutes
80 400 6 minutes
100 500 4.6 minutes
Environmental specifications
Feature Specification
Operating temperature
10°C to 40°C (50°F to 104°F); UL-tested at 25°C
(77°F)
Nonoperating
temperature
-25°C to 55°C (-13°F to 131°F)
Relative humidity 20% to 80%; noncondensing
Operating altitude Up to 2,000 m (6,600 ft) above sea level
Nonoperating altitude Up to 15,000 m (49,212 ft) above sea level
Audible noise Less than 45 dBA, normal operation
Less than 50 dBA, on battery power

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HP T750 and is the answer not in the manual?

HP T750 Specifications

General IconGeneral
Output Voltage230V
Input Voltage230V
Interface PortUSB
Waveform TypeStepped approximation to a sinewave
Nominal output voltage230V
Nominal input voltage230V
Battery TypeSealed lead-acid (VRLA)
TopologyLine Interactive
Input frequency50/60 Hz
Output ConnectionsIEC 320 C13
Input connection typeIEC 320 C14
Typical recharge time8 hours
Audible alarmYes
Operating Temperature0 - 40 °C
ApprovalsCE
Frequency50/60 Hz
Control panelLED status indicators
Operating Relative Humidity5% to 95% non-condensing