Alarm
ID
Alarm
Name
Severi
ty
Possible Cause Suggestion
2033 Grid
Undervolta
ge
Major Cause ID = 1
The grid voltage is below the
lower threshold or the low
voltage duration has lasted for
more than the value specied
by LVRT.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The device
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid voltage is
within the allowed range. If
not, contact the local power
operator. If yes, modify the
power grid undervoltage
protection threshold after
obtaining the consent of the
local power operator.
3. If the fault persists for a
long time, check the
connection between the AC
switch and the power cable.
2034
Grid
Overvoltag
e
Major Cause ID = 1
The grid voltage exceeds the
higher threshold or the high
voltage duration has lasted for
more than the value specied
by HVRT.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The device
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid voltage is
within the allowed range. If
not, contact the local power
operator. If yes, modify the
power grid overvoltage
protection threshold after
obtaining the consent of the
local power operator.
3. Check whether the peak
voltage of the power grid is
too high. If the fault occurs
frequently and persists for a
long time, contact the local
power operator.
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 8 Alarm Reference