Alarm
ID
Alarm
Name
Severi
ty
Possible Cause Suggestion
2035 Grid
Voltage
Imbalance
Major Cause ID = 1
The dierence between grid
phase voltages exceeds the
upper threshold.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The device
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid voltage is
within the normal range. If
not, contact the local power
operator.
3. If the fault persists for a
long time, check the
connection of the AC cable.
4. If the AC cable is correctly
connected and the alarm
persists and
aects the
operation of the plant,
contact the local power
operator.
2036
Grid
Overfreque
ncy
Major Cause ID = 1
Power grid exception: The
power grid frequency is higher
than the frequency required in
the local standard.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The device
automatically recovers after
detecting that the power
grid becomes normal.
2. If the alarm occurs
frequently, check whether
the power grid frequency is
within the allowed range. If
not, contact the local power
operator. If yes, modify the
power grid overfrequency
protection threshold after
obtaining the consent of the
local power operator.
LUNA2000-100KTL-M1 Smart Power Control System
User Manual 8 Alarm Reference
Issue 02 (2023-01-10) Copyright © Huawei Technologies Co., Ltd. 88