EasyManua.ls Logo

Huawei LUNA2000-200KTL-H0 - B Crimping an OT or DT Terminal

Huawei LUNA2000-200KTL-H0
115 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
B Crimping an OT or DT Terminal
Requirements for OT/DT terminals
If a copper cable is used, use copper wiring terminals.
If a copper-clad aluminum cable is used, use copper wiring terminals.
If an aluminum alloy cable is used, use copper-to-aluminum wiring terminals,
or aluminum wiring terminals with copper-to-aluminum washers.
NO TICE
Do not connect aluminum wiring terminals directly to the AC or DC terminal
block, as this may lead to electrochemical corrosion which
aects the reliability
of cable connections.
Comply with IEC 61238-1 requirements when using copper-to-aluminum wiring
terminals, or aluminum wiring terminals with copper-to-aluminum washers.
Ensure that the aluminum side of the washer contacts the aluminum wiring
terminal, and the copper side contacts the terminal block.
LUNA2000-200KTL-H0 Smart Power Control System
User Manual B Crimping an OT or DT Terminal
Issue 05 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 102

Table of Contents

Related product manuals