No. Category Parameter Description Remarks
9 Reactive power
mode when
communication
fails
Species the protection
threshold of the reactive
power after communication is
interrupted, including Q/S
and power factor.
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable.
10 Reactive power
threshold when
communication
fails (%)
Species the Q/S threshold of
the reactive power (%)
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and
Reactive power
threshold when
communication
fails is set to Q/S.
11 Reactive power
threshold when
communication
fails
Species the power factor
threshold of the reactive
power (PF)
This parameter is
displayed when the
protection in the
case of
communication
failure is set to
Enable and
Reactive power
threshold when
communication
fails is set to Power
factor.
12 Soft start time Soft start time
(s)
Species the duration
required for gradual power
increase when the device
starts.
-
13 Shutdown
gradient
Shutdown
gradient (%/s)
Species the power change
rate when the device shuts
down.
-
14 Auto shutdown
settings
Shutdown at 0%
power limit
If this parameter is set to
Enable, the device shuts
down after receiving the 0%
power limit command. If this
parameter is set to Disable,
the device does not shut
down after receiving the 0%
power limit command.
-