No. Category Parameter Description Remarks
33 VRT active
power recovery
gradient
Species the recovery rate
when the active current
recovers to the value at the
moment before FRT.
-
34 Zero current due
to power grid
fault
Species whether to enable
the Zero current due to
power grid fault function.
-
35 Zero current due
to power grid
fault
This parameter can only be
set for the VDE4120.
-
36 Voltage rise
suppression P-U
curve
Voltage rise
suppression
The standards of certain
countries and regions require
that when the output voltage
exceeds a certain value, the
device must suppress a rise in
voltage by outputting reactive
power and reducing active
power.
-
37 Voltage rise
suppression
reactive
adjustment
point (%)
The standards of certain
countries and regions require
the device to generate a
certain amount of reactive
power when the output
voltage exceeds a certain
value.
● This parameter is
displayed when
Voltage rise
suppression is set
to Enable.
● The value of
Voltage rise
suppression
active derating
point must be
greater than that
of Voltage rise
suppression
reactive
adjustment
point.
38 Voltage rise
suppression
active derating
point (%)
The standards of certain
countries and regions require
the active power of the device
to be derated by a certain
slope when the output
voltage exceeds a certain
value.
-