No. Category Parameter Description Remarks
33 VRT active
power recovery
gradient
Species the recovery rate
when the active current
recovers to the value at the
moment before FRT.
-
34 Zero current due
to power grid
fault
Species whether to enable
the Zero current due to
power grid fault function.
-
35 Zero current due
to power grid
fault
This parameter can only be
set for the VDE4120.
-
36 Voltage rise
suppression P-U
curve
Voltage rise
suppression
The standards of certain
countries and regions require
that when the output voltage
exceeds a certain value, the
device must suppress a rise in
voltage by outputting reactive
power and reducing active
power.
-
37 Voltage rise
suppression
reactive
adjustment
point (%)
The standards of certain
countries and regions require
the device to generate a
certain amount of reactive
power when the output
voltage exceeds a certain
value.
This parameter is
displayed when
Voltage rise
suppression is set
to Enable.
The value of
Voltage rise
suppression
active derating
point must be
greater than that
of Voltage rise
suppression
reactive
adjustment
point.
38 Voltage rise
suppression
active derating
point (%)
The standards of certain
countries and regions require
the active power of the device
to be derated by a certain
slope when the output
voltage exceeds a certain
value.
-
LUNA2000-200KTL-H0 Smart Power Control System
User Manual 8 Device Commissioning
Issue 05 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 65

Table of Contents