No. Category Parameter Description Remarks
2 Schedule
instruction valid
duration (s)
Species the validity period of
the scheduling instruction.
When this
parameter is set
to 0, the
scheduling
instruction
takes
eect
permanently.
3 Active power Active power
change gradient
(%/s)
Species the change rate of the
device's active power.
-
4 Active power (kW) Species the xed active power
of the device.
-
5 Active power (%) Species the active power of the
device in percent.
-
6 Reactive power Reactive power
change gradient
(%/s)
Species the change rate of the
device's reactive power.
-
7 Power factor Species the power factor of the
device.
-
8 Reactive power
compensation
(Q/S)
Species the reactive power of
the device.
-
9 Q-U
characteristic
curve
Q-U characteristic
curve
The device adjusts Q/S (the ratio
of the output reactive power to
apparent power) in real time
based on U/Un(%) (the ratio of
the actual power grid voltage to
the rated power grid voltage).
-
10 Q-U characteristic
curve mode
Species the reactive power
compensation mode of the
device output.
-
11 Delay for Q-U
characteristic curve
to take eect
Species the delay time for Q-U
adjustment.
-
12 Power percentage
for triggering Q-U
scheduling
Species the reference apparent
power in percent. When the
actual apparent power of the
device is greater than the value
of this parameter, the Q-U
characteristic curve scheduling
function is enabled.
-
LUNA2000-200KTL-H0 Smart Power Control System
User Manual 8 Device Commissioning
Issue 05 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 70