Check Item Check Method Maintenance
Interval
System running
status
Check that the Smart PCS is not
damaged or deformed.
Check that the Smart PCS
operates with no abnormal
sounds.
Check that the parameters are
set correctly.
Once every 6 months
Cable
connections
Check that cables are secured.
Check that cables are intact,
and ensure that any parts in
contact with metallic surfaces
are not scratched.
Check that the idle COM, USB,
and FE ports are protected by
waterproof caps.
The rst inspection
must be performed 6
months after the
initial commissioning.
Subsequent
inspections can be
performed every 6 to
12 months.
Grounding
reliability
Check that ground cables are
securely connected.
The rst inspection
must be performed 6
months after the
initial commissioning.
Subsequent
inspections can be
performed every 6 to
12 months.
Removing the Air Inlet
Bae
Figure 9-1 Removing the bae
NO TICE
After cleaning is complete, reinstall the air inlet bae. Tighten the screws to a
torque of 1.2 N·m.
LUNA2000-200KTL-H0 Smart Power Control System
User Manual 9 Device Maintenance
Issue 05 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 73