Figure 4-10 Setting battery control parameters
Parameter Description
Working mode Set this parameter to Charge/Discharge based on grid
dispatch.
Automatic SOC
calibration
● If this parameter is set to Disable, automatic charge and
discharge calibration is not allowed for battery racks.
● If this parameter is set to Enable, automatic charge and
discharge calibration is allowed for battery racks. The
ESS periodically calibrates the SOC rack by rack. During
the calibration, the end-of-charge SOC and end-of-
discharge SOC settings will be overridden so that the
ESS can be fully charged or discharged.
– On-grid scenario: Automatic charge calibration is
allowed for battery racks.
– O-grid scenario: Automatic discharge calibration is
allowed for battery racks.
Automatic SOH
calibration
Set this parameter to Disable.
Detection start
time
Set the start time of the PCS insulation resistance
detection.
If a dialog box You are advised to change the insulation
resistance detection time to the optimal time:
XX:XX
is
displayed, you are advised to click Conrm and set
Detection start time to the optimal time. SmartLogger
V300R023C00SPC172 and later versions support this
function.
Step 7 Connect to a Huawei network management system (NMS).
Set related parameters by referring to "Setting Parameters for Connecting to
the Management System" (content related to a Huawei NMS) in the
SmartLogger3000 User Manual
.
Commercial and Industrial Microgrid Energy Storage
Solution
Quick Guide (With Third-Party Microgrid Central
Controller) 4 System Power-On and Commissioning
Issue 04 (2023-12-18) Copyright © Huawei Digital Power Technologies Co., Ltd. 32