PowerCube 5000
User Manual (SmartLi 100Ah)
5 Power-on Commissioning
Copyright © Huawei Technologies Co., Ltd.
101
Item
Parameter
Setting
Output Volt Adjust
(V)
Altitude (m)
EPO enable
EPO (emergency power-off) is performed only
when this parameter is enabled and the EPO switch
is triggered.
When EPO detection is changed from Disable to
Enable, check that the EPO cable is connected
correctly.
AC Phase Detect
(displayed in a
parallel system)
Start
If the detection result is abnormal, alarms AC
Input Phase Sequence Incorrect and AC Output
Phase Sequence Incorrect will be generated on the
MDU and WebUI. In this case, reconnect the
cables.
Network
parameters
IP Address
Set this parameter according to the address
information provided by the network administrator.
Set the IP addresses of master and slave cabinets on
the same network segment in the parallel scenario.
Subnet Mask
Default Gateway
Lihv battery equip IP
The IP address of the lithium battery cabinet must
be the same as the lithium battery cabinet IP
address set for the ICC cabinet.
Step 2 Set communications parameters for other devices on the MDU of the master cabinet.
Table 5-3 Setting communications parameters
Path
Parameter
Setting
System Info >
Settings >
Communication
Monitor Parallel IP (for a
parallel system)
IP address of the slave cabinet
Lihv Battery Equip IP
IP address of the lithium battery
cabinet
NetEco Primary IP
Set this parameter according to the
address information provided by
the network administrator.
NetEcoPort Number
Set this parameter as required.
Step 3 (For a parallel system) On the MDU of the master cabinet, choose System Info > Settings >
Basic Param, and set Transformer Cabinet SPD Fault Alm. Cond. to Close.
----End