Step 3 Switch on the battery cold-start circuit breaker (QF2) in the lithium battery cabinet.
Step 4 If the ICC cabinet is powered off, power on the ICC cabinet.
----End
Clearing the EPO State for the Lithium Battery Cabinet
Step 1 Check whether the lithium battery cabinet is powered off. If so, switch on the battery
cold-start circuit breaker (QF2) in the lithium battery cabinet.
Step 2 Rotate the EPO button on the front door of the lithium battery cabinet clockwise until the
button ejects to clear the EPO state.
Step 3 Check that the EPO alarm is cleared.
----End