PowerCube 5000
User Manual (SmartLi 100Ah)
Copyright © Huawei Technologies Co., Ltd.
actual number.
3. The actual number
of batteries does not
meet specifications.
PV Input
Insulation Fault
DC/DC
Converter
Communication
Failure
The rectifier chip fails
to communicate.
Replace the power unit or module.
Inverter
Communication
Failure
The inverter chip fails
to communicate.
Replace the power unit or module.
Ambient Low
Temperature
Protection
The ambient
temperature is below
–33°C.
Ensure that the ambient temperature is
higher than –22°C.
Replace the power unit or module.
The module ready
switch is not turned on.
Turn on the module ready switch.
Ambient
Overtemperatur
e Protection
The ambient
temperature exceeds
85°C.
Check whether the alarm is
automatically cleared 5 minutes after the
ambient temperature falls below 85°C.
RCD Leakage
Current
Exceeded
1. Check whether the insulation layer
for PV input is damaged.
2. Replace the power unit or module.
All Inverters
Communication
Failure
All inverter chips fail to
communicate.
Replace the power unit or module.
DC/DC
Converter
Communication
Failure
All inverters shut down
in emergency.
Replace the power unit or module.
Inverter
Configuration
Failure
Parallel configuration
of rectifiers and
inverters fail.
Replace the power unit or module.
All DC/DC
Converters
Communication
All rectifier chips fail
to communicate.
Replace the power unit or module.