PowerCube 5000
User Manual (SmartLi 100Ah)
Copyright © Huawei Technologies Co., Ltd.
The board component
has deteriorated.
Check whether the output port voltage is
normal using a multimeter.
The board component
has deteriorated.
Check whether the output port voltage is
normal using a multimeter.
The board power
wiring is incorrect.
Check whether the wiring sequence is
correct.
The board power
wiring is incorrect.
Check whether the wiring sequence is
correct.
1. The
communications
cable is faulty.
2. The address is
incorrectly set.
3. The
communications
port is faulty.
4. The communication
expansion board is
faulty.
1. Rectify the faults on the
communications cable, such as cable
damage, loose connectors, bent pins,
or misplaced pins. Then check
whether the alarm is cleared.
2. Check whether the communications
address is correctly set. If the address
is incorrect, correct the address and
check whether the alarm is cleared.
3. Replace the communications board,
and check whether the alarm is
cleared.
4. Replace the IS03/IS04 converter and
check whether the alarm is cleared.
Energy
control
and
managem
ent
Replace the ECM in the first slot.
The DSP and CPLD of
the centralized
controller fail to
communicate.
Replace the power unit or module.
Abnormal
Parallel Cable
In The Power
Cabinet
The intra-rack parallel
CAN is faulty.
1. Check whether the parallel board
connector is loose.
2. Replace the power unit or module.
3. Replace the parallel cable.
4. Replace the parallel board.
The DSP version of the
central controller does
not match the power
hardware version.
Abnormal
Parallel Cable
Between The
Power Cabinets
Intra-rack
industrial-frequency
synchronization is
abnormal.
1. Check whether the parallel board
connector is loose.
2. Replace the power unit or module.
3. Replace the parallel cable.
4. Replace the parallel board.
1. Manually clear the alarm.