PowerCube 5000
User Manual (SmartLi 100Ah)
2 Products
Copyright © Huawei Technologies Co., Ltd.
40
Easy supply: Lithium battery cabinets can be delivered without ESM configuration.
Easy transportation: ESMs and lithium battery cabinets can be transported separately and
assembled onsite, which effectively solves the transportation problem for remote
microgrid sites.
Easy maintenance: Old and new ESMs can be used together. You do not need to
manually charge or discharge the replacement ESMs to adjust the capacity.
Figure 2-24 Product structure
(1) Alarm indicator
(2) Running indicator
(3) EPO button
(4) SBCU
(5) ESMs
(6) BCU
(7) Battery breaker
(QF1)
(8) BCU power switch
(QS1)
(9) Battery cold-start breaker
(QF2)
Table 2-32 Indicator description
Name
Color
Status
Meaning
RUN
Green
On
Communication is normal.
Off
Batteries are powered off or hibernating.
Blinking
slowly
Frequency 0.5 Hz: standby
Blinking fast
Frequency 2 Hz: communication failure
ALM
Red
On
A fault or major alarm is generated.
Off
No fault or major alarm is generated.