Alarm
ID
Alarm Name Alarm
Severity
Possible Causes Troubleshooting
2033 Grid
Undervoltage
Major Cause ID = 1
The grid voltage is below
the lower threshold or the
low voltage duration has
lasted for more than the
value
specied by low
voltage ride-through
(LVRT).
1. If the alarm occurs
occasionally, the power
grid may be abnormal
temporarily. The
SUN2000 automatically
recovers after detecting
that the power grid
becomes normal.
2. If the alarm occurs
frequently, check
whether the power grid
voltage is within the
allowed range. If no,
contact the local power
operator. If yes, modify
the grid undervoltage
protection threshold
through the mobile App,
SmartLogger, or network
management system
(NMS) with the consent
of the local power
operator.
3. If the fault persists for a
long time, check the
connection between the
AC switch and the
output power cable.
SUN2000-(2KTL-6KTL)-L1
User Manual 8 System Maintenance
Issue 10 (2023-02-13) Copyright © Huawei Technologies Co., Ltd. 92

Table of Contents

Other manuals for Huawei SUN2000-4KTL-L1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000-4KTL-L1 and is the answer not in the manual?

Huawei SUN2000-4KTL-L1 Specifications

General IconGeneral
Max. efficiency98.4%
Max. input voltage600 V
Rated output power4000 W
Dimensions (W x H x D)365 x 365 x 156 mm
Max. apparent AC power4000 VA
Nominal AC voltage220 V / 230 V / 240 V
MPPT voltage range200-1000 V
Number of MPP trackers2
Max. short-circuit current per MPPT15 A
Operating temperature range-25°C to +60°C
Protection degreeIP65
Max. Input Power6000 W
Max. Output Power4000 W
Rated Output Voltage220 V / 230 V / 240 V
Output Frequency50 Hz / 60 Hz
Cooling MethodNatural convection
AC voltage range180 V to 280 V