Power grid exception: The actual grid
frequency is higher than the
requirement of the local power grid
standard.
1. If the alarm occurs
accidentally, the power grid
may be abnormal temporarily.
The SUN2000 automatically
recovers after detecting that the
power grid becomes normal.
2. If the alarm occurs frequently,
check whether the grid
frequency is within the
acceptable range. If no, contact
the local power operator. If
yes, modify the power grid
overfrequency protection
threshold with the consent of
the local power operator.
Power grid exception: The actual
power grid frequency is lower than the
standard requirement for the local
power grid.
1. If the alarm occurs
accidentally, the power grid
may be abnormal temporarily.
The SUN2000 automatically
recovers after detecting that the
power grid becomes normal.
2. If the alarm occurs frequently,
check whether the grid
frequency is within the
acceptable range. If no, contact
the local power operator. If
yes, modify the power grid
underfrequency protection
threshold with the consent of
the local power operator.
Power grid exception: The actual grid
frequency change rate does not comply
with the local power grid standard.
1. If the alarm occurs
accidentally, the power grid
may be abnormal temporarily.
The SUN2000 automatically
recovers after detecting that the
power grid becomes normal.
2. If the alarm occurs frequently,
check whether the grid
frequency is within the
acceptable range. If no, contact
the local power operator.