SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
7 Man-Machine Interactions
Copyright © Huawei Technologies Co., Ltd.
84
No.
Parameter
Description
Unit
Value Range
Remarks
10
Voltage rise
suppression
The standards of certain
countries and regions
require that the SUN2000
should prevent the grid
voltage from rising by
delivering reactive power
and decreasing active
power when the output
voltage exceeds a certain
value.
N/A
Disable
Enable
N/A
11
Voltage rise
suppression
reactive
adjustment
point
The standards of certain
countries and regions
require that the SUN2000
must generate a certain
amount of reactive power
when the output voltage
exceeds a certain value.
%
[100, 115]
This parameter is
displayed when
Voltage rise
suppression is set
to Enable.
The value of
Voltage rise
suppression active
derating point
must be greater
than that of Voltage
rise suppression
reactive
adjustment point.
12
Voltage rise
suppression
active
derating point
The standards of certain
countries and regions
require that the active
power of the SUN2000 be
derated according to a
certain gradient when the
output voltage exceeds a
certain value.
%
[100, 115]
13
Soft start
time after
grid failure
Specifies the time for the
power to gradually increase
when the SUN2000 restarts
after the power grid
recovers.
s
[20, 800]
N/A
7.2.2.4 Setting Power Adjustment Parameters
Procedure
Step 1 Choose Function Menu > Settings > Power Adjustment to access the settings screen.