SUN2000-(50KTL-JPM0, 50KTL-JPM1, 63KTL-JPM0)
User Manual
5 Electrical Connections
Copyright © Huawei Technologies Co., Ltd.
37
Table 5-1 AC Power Cable Specifications
Cable Specifications
Copper-Core Cable
Copper-Clad
Aluminum Cable or
Aluminum Alloy
Cable
Conductor
cross-sectional area
(mm
2
)
Range
2270
3870
Recomme
nded
value
38
60
Table 5-2 Ground cable specifications
Cross-Sectional Area S (mm
2
) of the
AC Power Cable Conductor
Cross-Sectional Area S
P
(mm
2
) of the
PE Cable Conductor
16 < S ≤ 35
S
P
≥ 16
35 < S
S
P
≥ S/2
The values in this table are valid only if the PE cable and AC power cable use the same
conductor material. If this is not so, the cross-sectional area of the PE cable conductor is to
be determined in a manner which produces a conductance equivalent to that which results
from the application of this table.
Installing the PE Cable
Step 1 Crimp an OT terminal.
Step 2 Secure the PE cable using the ground screw.
Figure 5-7 Connecting a PE cable