Figure 5-3 Connecting the PE cable
(1) Reserved PE point
----End
5.4 Connecting the AC Output Power Cable
Precautions
An AC switch must be installed on the AC side of the SUN2000 to ensure that the
SUN2000 can be safely disconnected from the power grid.
● Do not connect loads between the inverter and the AC switch that directly
connects to the inverter. Otherwise, the switch may trip by mistake.
● If an AC switch is used with
specications beyond local standards, regulations,
or the Company's recommendations, the switch may fail to turn
o in a timely
manner in case of exceptions, causing serious faults.
Each inverter must be equipped with an AC output switch. Multiple inverters
cannot connect to the same AC output switch.
SUN2000-(50KTL-ZHM3, 50KTL-M3)
User Manual 5 Electrical Connections
Issue 05 (2023-02-28) Copyright © Huawei Technologies Co., Ltd. 38