Figure 7-8 Power adjustment parameters (special user)
----End
Parameter List
Table 7-5 Parameter description
Parameter
Description Remarks
Remote power
schedule
If this parameter is set to Enable, the
SUN2000 responds to the remote
power scheduling instruction. If this
parameter is set to Disable, the
SUN2000 does not respond to the
remote power scheduling instruction.
N/A
Schedule instruction
valid duration (s)
Species the duration within which the
scheduling instruction is valid.
If the value is less than 60
seconds, the scheduling
instruction is valid permanently.
Maximum active
power (kW)
Sets the upper threshold for the active
power output to adapt to dierent
market requirements.
Pmax_limit: upper threshold for
the active power output
Apparent power
baseline (kVA)
Adjusts the apparent output baseline
of the inverter.
N/A
Active power
baseline (kW)
Adjusts the active output baseline of
the inverter.
N/A
SUN2000-(70KTL, 75KTL)-C1
User Manual 7 Man-Machine Interactions
Issue 09 (2020-10-12) Copyright © Huawei Technologies Co., Ltd. 92