Alarm
ID
Alarm
Name
Alarm
Severity
Cause Measures
2034 Grid
Overvol
tage
Major Cause ID = 1
The grid voltage exceeds the
higher threshold or the high
voltage duration has lasted for
more than the value specied by
HVRT.
1. Check whether the grid
connection voltage exceeds
the upper threshold. If yes,
contact the local power
operator.
2. If you have
conrmed that
the grid connection voltage
exceeds the upper
threshold and obtained the
consent of the local power
operator, modify the
overvoltage protection
threshold.
3. Check that the peak grid
voltage does not exceed
the upper threshold.
2035 Grid
Voltage
Imbala
nce
Major Cause ID = 1
The dierence between grid phase
voltages exceeds the upper
threshold.
1. Check that the grid voltage
is within the normal range.
2. Check the connection of
the AC output power cable.
If the cable connection is
proper but the alarm
occurs frequently and
aects the power
production of the PV plant,
contact the local power
operator.
2036 Grid
Overfre
quency
Major Cause ID = 1
Power grid exception: The actual
grid frequency is higher than the
requirement of the local power
grid standard.
1. If the alarm occurs
accidentally, the power grid
may be abnormal
temporarily. The SUN2000
automatically recovers
after detecting that the
power grid becomes
normal.
2. If the alarm occurs
frequently, check whether
the grid frequency is within
the acceptable range. If no,
contact the local power
operator. If yes, modify the
power grid overfrequency
protection threshold with
the consent of the local
power operator.
SUN2000-(70KTL, 75KTL)-C1
User Manual 8 Maintenance
Issue 09 (2020-10-12) Copyright © Huawei Technologies Co., Ltd. 100