No. Parameter Description
1 Unbalance voltage
protection threshold
(%)
Species the inverter protection threshold when the power grid
voltage is unbalanced.
2 Insulation resistance
protection threshold
(MΩ)
To ensure device safety, the inverter detects the insulation
resistance of the input side with respect to ground when it
starts a self-check. If the detected value is less than the preset
value, the inverter does not connect to the grid.
4 Phase angle oset
protection
The standards of certain countries and regions require that the
inverter needs to be protected when the phase angle oset of
the power grid three phases exceeds a certain value.
5 Voltage threshold for
10-minute overvoltage
protection (V)
Species the 10-minute overvoltage protection threshold.
6 Duration threshold for
10-minute overvoltage
protection (ms)
Species the 10-minute overvoltage protection duration.
7 Level-1 overvoltage
protection threshold
(V)
Species the level-1 grid overvoltage protection threshold.
8 Duration threshold for
level-1 overvoltage
protection (ms)
Species the level-1 grid overvoltage protection duration.
9 Level-1 undervoltage
protection threshold
(V)
Species the level-1 grid undervoltage protection threshold.
10 Duration threshold for
level-1 undervoltage
protection (ms)
Species the level-1 grid undervoltage protection duration.
11 Level-2 undervoltage
protection threshold
(V)
Species the level-2 grid undervoltage protection threshold.
12 Duration threshold for
level-2 undervoltage
protection (ms)
Species the level-2 grid undervoltage protection duration.
13 Level-1 overfrequency
protection threshold
(Hz)
Species the level-1 grid overfrequency protection threshold.
14 Duration threshold for
level-1 overfrequency
protection (ms)
Species the level-1 grid overfrequency protection duration.
15 Level-1 underfrequency
protection threshold
(Hz)
Species the level-1 grid underfrequency protection threshold.
16 Duration threshold for
level-1 underfrequency
protection (ms)
Species the level-1 grid underfrequency protection duration.
17 Active islanding
protection
Species whether to enable the active islanding protection
function.
SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual 7 Man-Machine Interactions
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 72