Alarm
ID
Alarm
Name
Alarm
Severity
Possible Cause Suggestion
61440 Faulty
Monitori
ng Unit
Minor Cause ID = 1
1. The ash memory is
insucient.
2. The ash memory has bad
sectors.
Turn o the AC output switch
and then the DC input
switches. After 5 minutes,
turn them on in the same
sequence. If the fault persists,
replace the monitoring board,
or contact your dealer or
technical support.
NO TE
If you cannot rectify the fault using the recommended method in the Suggestion column,
contact your dealer or technical support.
8.5 Replacing a Fan
CA UTION
Before replacing a fan, power o the inverter.
When replacing a fan, use insulation tools and wear personal protective
devices.
NO TE
If the fan tray gets stuck when being pulled or pushed, slightly lift it.
Step 1 Remove the screw on the fan tray and save it. Pull out the fan tray until the fan
bae plate aligns with the inverter chassis.
Figure 8-3 Pulling out fan tray (1)
Step 2 Remove the cable ties shared by the cables, unscrew the connectors, and
disconnect the cables.
SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual 8 Maintenance
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 104

Table of Contents

Other manuals for Huawei SUN2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000 Series and is the answer not in the manual?

Huawei SUN2000 Series Specifications

General IconGeneral
Max Efficiency98.6%
MPPT Efficiency99.9%
Protection RatingIP65
Max. DC Voltage1100 V
Rated AC Frequency50 Hz / 60 Hz
Rated Power3kW - 10kW
Operating Temperature Range-25 °C ~ +60 °C
CommunicationRS485
Rated AC Power3kW - 10kW
Power Factor Adjustment Range0.8 leading to 0.8 lagging
Total Harmonic Distortion (THD)≤ 3%
ProtectionDC reverse polarity
CoolingNatural convection
DC ConnectionMC4

Related product manuals