No. Parameter Description Remarks
15 Quit frequency of
overfrequency
derating (Hz)
overfrequency derating
Trigger frequency of
overfrequency derating <
Cuto frequency of
overfrequency derating.
Species the frequency threshold
for exiting overfrequency
derating.
16 Cuto frequency of
overfrequency
derating (Hz)
Species the frequency threshold
for cutting o overfrequency
derating.
17 Cuto power of
overfrequency
derating (%)
Species the power threshold for
cutting o overfrequency
derating.
18 Power recovery
gradient of
overfrequency
derating (%/min)
Species the recovery rate of the
overfrequency derating power.
19 PF-U voltage
detection ltering
time (s)
Species the time for ltering the
grid voltage in the PF-U curve.
-
20 Active power
baseline (kW)
Adjusts the active output baseline
of the inverter.
The apparent power baseline
must be greater than or equal
to the active power baseline.
21 Apparent power
baseline (kVA)
Adjust the apparent output
baseline of the inverter.
22 Communication
disconnection fail-
safe
In the inverter export limitation
scenario, if this parameter is set
to Enable, the inverter will
perform active power derating by
percentage when the
communication between the
inverter and the SmartLogger or
Smart Dongle is disconnected for
more than the time
specied by
Communication disconnection
detection time.
-
23 Communication
disconnection
detection time (s)
Species the fail-safe detection
time for the disconnection
between the inverter and the
SmartLogger or Smart Dongle.
This parameter is displayed
when Communication
disconnection fail-safe is set
to Enable.
24 Active power mode
when
communication
fails
Species the protection threshold
of the active power after
communication is interrupted.
The value can be a percentage or
a xed value.
SUN2000-(100KTL, 110KTL, 115KTL)-M2
User Manual 7 Man-Machine Interactions
Issue 02 (2022-06-30) Copyright © Huawei Technologies Co., Ltd. 82

Table of Contents

Other manuals for Huawei SUN2000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei SUN2000 Series and is the answer not in the manual?

Huawei SUN2000 Series Specifications

General IconGeneral
Max Efficiency98.6%
MPPT Efficiency99.9%
Protection RatingIP65
Max. DC Voltage1100 V
Rated AC Frequency50 Hz / 60 Hz
Rated Power3kW - 10kW
Operating Temperature Range-25 °C ~ +60 °C
CommunicationRS485
Rated AC Power3kW - 10kW
Power Factor Adjustment Range0.8 leading to 0.8 lagging
Total Harmonic Distortion (THD)≤ 3%
ProtectionDC reverse polarity
CoolingNatural convection
DC ConnectionMC4