UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
4 User Interface
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
144
Item
Description
IP address
Set an Ethernet IP address that ranges from 1.0.0.0 to
223.255.255.255. The default value is 192.168.0.10.
NOTICE
Ensure that the UPS IP address is unique on the network segment. Otherwise,
the WebUI display function may not function properly.
Subnet mask
Set an Ethernet subnet mask that ranges from 0.0.0.0 to
255.255.255.255. The default value is 255.255.255.0.
Gateway
Set an Ethernet gateway that ranges from 1.0.0.0 to 223.255.255.255.
The default value is 192.168.0.1.
NAT mapping
NAT means network address translation. If it is set to Disable, an
internal IP address cannot be accessed from the Internet.
RS485 com. baud
rate
Baud rate depends on the network management conditions.
Figure 4-32 Communication screen 2
Item
Description
RS485
com.
address
Set an address that ranges from 1 to 254 for this port.
Parity
mode
Verify the validity of RS485 communication characters. When a device
node adopts RS485 communication, ensure that the parity modes for the
device nodes are set to the same mode. Available parity modes include
None, Odd, and Even.
Stop bit
Stop bit in the Modbus communication frame format. When the UPS is
connected over the serial port Modbus, set this parameter based on the
frame format that the upstream device Modbus supports.
Batt. temp.
A maximum of four battery temperature sensors can be cascaded.