UPS5000-E-(50 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Figure 4-46 Battery Param. screen 4
An alarm is generated if this parameter is set to Enable and
the backup time is lower than the warning threshold.
An alarm is generated if this parameter is set to Enable and
the remaining capacity is lower than the warning threshold.
Dis. cur. 0.1C EOD
(V/cell), Dis. cur. 0.3C
EOD (V/cell), Dis. cur.
0.5C EOD (V/cell), and
Dis. cur. 1.0C EOD
(V/cell)
By default, 0.1C EOD (V/cell) is set to 1.80, 0.3C EOD
(V/cell) to 1.75, 0.5C EOD (V/cell) to 1.67, and 1.0C EOD
(V/cell) to 1.60. These values are calculated in real time based
on the discharge currents.
Figure 4-47 Battery Param. screen 5